NANO 300

Rugged & Reliable, Repeatable & Predicable
Designed for both control rooms and field mounting (-40 °C to +85 °C)
Low Power for a cool and reliable long service life
MID approvals from NMi & NMRO
Compact size simplifies refits and reduces cost of new installations

NÅNO Flow Computer


Digital Status Inputs – 9 off


  • Individually opto-isolated inputs
  • Maximum input voltage = 32 V
  • Minimum input on voltage = 10 V
  • Maximum input off voltage = 3 V
  • Input impedance 2 kΩ typical
  • Protection surge and reverse voltage protection
  • Fleeting input detection

Digital Status Outputs – 8 off


  • Individually optically isolated
  • Maximum output current = 100 mA
  • Maximum output saturation voltage = 2.1 V @ 100 mA
  • Maximum output standoff voltage = 32 V, limited by input protection
  • When powered off or reset, all digital outputs are OFF
  • Two outputs can be used as pulse outputs or PWM outputs
  • Frequency range is DC to 500 Hz
  • PWM mode 0% to 100% in 0.2% steps

Meter Pulse Inputs & Period Measurement – 4 off


  • Inputs can use differential or single ended inputs
  • Inputs are individually opto-coupled
  • Input signal levels from ±3.5 V to ±24 V
  • Input current minimum = 2.5 mA
  • Input impedance = 1 kΩ
  • Frequency range from DC to 10 kHz
  • Inputs A & B feature back-to-back optos, allowing full quiescent line and electronic integrity testing, when used with differential pre‑amps such as the ST106
  • Dual Pulse compliant inputs A & B support IP 252/76, ISO6551 or API Ch 5.5 level A or B, with line integrity, even when static
  • Accuracy of period measurement = 2.5 ppm
  • Period resolution = 5 ns

Raw Pulse Bus


  • Digital ground referenced differential transceiver
  • Enable & direction software controlled
  • Used to bus together multiple streams to a common prover
  • RS422 compatible drive & receive levels
  • Maximum output frequency 10 kHz

Alarm Relay


  • The relay used for the Gen3 hardware is a PhotoMOS solid state change-over relay
  • Both Form A (Normally Open) & Form B (Normally Closed) outputs provided
  • Maximum current 1 A (de-rated to 0.5 A for operation above 75 °C ambient)
  • Maximum voltage 32 V, limited by input protection
  • Isolation = 100 V
  • Released on de-power, watchdog restart or software command

Analogue Inputs – 6 off


  • Type of inputs: 1 to 5 Volt or 4-20 mA, differential inputs
  • All channels individually isolated to 50 V RMS in voltage and current input mode
  • Conversion Method: 24 bit Sigma-Delta ADC
  • Effective resolution: More than 18 bits, auto zero, auto calibrate
  • Conversion time: Less than 100 ms per channel
  • All channels can be acquired simultaneously
  • Series mode rejection: >100 dB at 50 Hz and 60 Hz
  • Voltage common mode range: ±50 V relative to computer ground or other input

RTD Inputs – 2 off


  • 4 wire Kelvin connection using Pt100 RTD
  • Temperature measuring range: -100 °C to +300 °C
  • Resolution: 0.01 °C
  • Accuracy: ±0.05 °C, -100 °C to +200 °C and ±0.1 °C, +200 °C to +300 °C
  • PRT cables loop resistance up to 600 Ω
  • Continuous cable integrity tests for excitation current and voltages allow open and short circuit detection
  • RTD current sources 1 mA nominal
  • 3 wire mode not supported
  • Each RTD uses one analog input channel

Analogue Outputs – 2 off


  • Each channel is individually isolated
  • Current controlled 0 to 24 mA
  • Can be used to sink or source power
  • Resolution: 14 bits
  • Accuracy: ±0.1% at 23 °C
  • Temperature Coefficient: 10 ppm / °C
  • Minimum load loop resistance: Safe down to 0 Ω from +32 V external supply
  • Maximum load loop resistance: 1 kΩ when powered from +24 V external
  • Maximum external supply: 32 V
  • Output form: Isolated active current controller
  • Number of field connections: 2 terminals per channel
  • Update time: 500 ms to within 1%

Hardware Overview

Mechanical


  • Length on Rail: 188mm
  • Height: 56mm
  • Width across Rail: 134mm
  • Weight: 650 grams
  • Structure: PVC extrusion with stainless steel lid
  • Mounting: 35mm symmetrical Top Hat rail to EN50022 and asymmetric G-type rail to EN50035

Environmental


  • -40°C to +85°C operating temperature range
  • -25°C to +55°C for MID certified installations
  • -60°C to +100°C storage (without integral display)
  • Humidity: Up to 95% non-condensing
  • Safety classification: For use in a safe area
  • High vibration tolerance due to robust mechanical design

Input Power


  • Input Voltage & Current: 11.5V to 30V DC, 4.5W nominal, 6W max
  • Suitable for 12V Solar powered systems
  • Digital only version is typically 3 Watts
  • DC Inputs: 2 off, allowing direct connection to redundant supplies
  • Galvanic isolation: Minimum of 50V RMS to Instrument Ground
  • Input Ripple: Maximum 2V peak to peak
  • Input protection: Non-replaceable 1A input fuse

Clock


  • Accuracy Powered-Off
    • Capacitor supported calendar better than 10 Seconds per day
    • Ensures logs and reports are in sequential time/date order following a power interruption
    • NOTE: Capacitor only supports up to 2 days powered off before clock is reset to last know power-off time
  • Accuracy Powered-On
    • 0.5 Seconds per day over full temperature range

Processor & Memory


  • CPU: 800 MHz ARM Cortex-A8 highly integrated SoC processor system
  • Memory
    • SRAM: Not required, by design, no batteries needed.
    • FRAM: 128 KBytes or 512 KBytes
    • NOR: Flash 128 MBytes
    • DRAM: 256 MBytes, DDR3 with 400MHz bus interface
  • Silicon Serial No: Globally unique 48 bit address and 2 Kbit EEPROM, 200 year retention

Communications


  • Four Serial ports
    • 1 x RS232
      Signals: TX, RX, RTS, CTS, GND
    • 1 x RS485 (2-wire), galvanically isolated
      Signals: A, B, Screen
    • 2 x RS422/RS485 (2-wire and 4-wire)
      Signals: TX+, TX-, RX+, RX-, Screen
  • Two Ethernet ports supporting 10/100MHz half & full duplex


Software Overview

Approvals


  • MID certified by both NMi and NMRO
  • OIML R117 Certified
  • EMC Directive 2014/30/EU
  • EU 2015/863 RoHS-3 directive
  • ISO9001 and AS9100 approved electronics manufacturers
  • Conflict Minerals compliant with RMI2020 and EU ‘Conflict Minerals’ Regulation (2017/821)

General


  • State-machine architecture based on a 500 ms application cycle time
  • Report storage
    • 6 zones, each with 1500 report slots
    • 10 zones, each with 250 report slots
  • Flexible report routing to send reports to printer(s), FTP and/or SD card
  • Alarm log storage
    • Set, Clear & Accept logged separately
    • 1500 log entries
  • Event log storage
    • System (1500 log entries)
    • Operator (2500 log entries)
    • Metrology (1500 log entries)
    • Security (1500 log entries)
    • Application (1500 log entries)
  • ALV (Additional Log Values)
    • Each Alarm or Event entry can also contain a snapshot of up-to 13 data-points
    • Useful for diagnostics, debugging or forensic analysis
  • Data Logging facility (aka “Historicals”)
    • Each data record supports up to 13 data-points
    • 3 “non-volatile” storage zones with 20,000 record slots
    • 1 further “volatile” zone with 86,400 record slots allowing logging every ½ second for 24 hours
    • Data can be downloaded as a TSV file
  • Support for three printers:
    • Printer #1 : Serial (CP437) or Networked
    • Printer #2 : Networked only
    • Printer #3 : Networked only

Integrated Web Server


  • View and download Reports, Alarms & Events using Calendar View
    • Download Reports as Text or PDF
    • Download Alarms & Events as TSV
  • View and download “historicals” data
  • Configure Date & Time manually or via NTP
  • Support for Time Zones
  • Support for Daylight Saving Time
  • Local Panel mimic for remote support
  • Browse contents of local SD card
  • Configure Printer settings
  • Configure Network settings