Digital Status Inputs - 9 off

  • Individually opto-isolated inputs
  • Maximum Input Voltage = 30V
  • Minimum Input on Voltage = 10V
  • Maximum Input off voltage = 3.0V
  • Input Impedance 2-2.5K Ohm typical
  • Protection Surge and reverse voltage protection
  • Additional Features Fleeting input detection provided

  • Digital Status Outputs - 8 off

  • Individually optically isolated
  • Max Output Current = 100mA
  • Max Output Saturation Voltage = 2.1V @ 100mA>
  • Max Output Standoff Voltage = 32V, limited by input protection
  • When off/Reset/Power on State All digital outputs OFF
  • Two outputs can be used as pulse outputs or PWM outputs
  • Frequency range is DC to 500Hz
  • PWM Mode 0% to 100% in 0.2% steps

  • Meter Pulse Inputs & Period Measurement – 4 off


  • Inputs can use differential or single ended inputs
  • All meter inputs are individually opto-coupled
  • Input signal levels from ± 3.5V to ± 24V
  • Input current minimum = 5mA
  • Input Impedance = 1K Ohm
  • Frequency range from DC to 10 kHz
  • Inputs A & B feature back-to-back optos, allowing full quiescent line and electronic integrity testing, when used with differential pre‑amps such as the ST106
  • Dual Pulse compliance Inputs A & B support IP 252/76, ISO6551 or API Ch 5.5 level A or B, with line integrity, even when static
  • Accuracy of period measurement 2.5 ppm
  • Period resolution 5 Nanoseconds
  • Raw Pulse Bus

  • Configuration Digital Ground referenced Differential transceiver
  • Gating & Direction software controlled
  • Use to bus together multiple streams to a common prover
  • Signalling RS422 Compatible drive & receive levels
  • Max output frequency 10 kHz

  • Alarm Relay


  • The relay used for the Gen3 hardware is a PhotoMOS solid state change-over relay
  • Contact Form Both Form A (Normally Open) & Form B (Normally Closed)
  • Max current 1A (de-rate to 0.5A for operation above 75°C ambient)
  • Max Voltage 32V, limited by input protection
  • Isolation 100V

  • Control Released on de-power or watchdog restart or software command
  • Analogue Inputs – 6 off


  • Type of Inputs: 1 to 5 Volt or 4-20 mA, Differential inputs
  • All channels individually isolated to 50V RMS in voltage and current input mode
  • Conversion Method: 24 bit Sigma-Delta ADC
  • Effective resolution: More than 18 bits, auto zero, auto calibrate
  • Conversion time: Less than 100 mSec per channel
  • All channels can be acquired simultaneously
  • Series mode rejection: >100 dB at 50 Hz and 60 Hz
  • Voltage Common mode range: ± 50V relative to computer ground or other input
  • Calibration Period 3 Years to ± 0.02% of reading
  • RTD Inputs – 2 off


  • 4 wire Kelvin connection using Pt 100 RTD
  • Temperature measuring range: -100°C to +300°C
  • Resolution: 0.01°C
  • Accuracy: ± 0.05°C, -100°C to +200°C and ± 0.1°C, +200°C to +300°C/li>
  • PRT cables Loop resistance up to 600 Ohms
  • Continuous cable integrity tests for excitation current and voltages allow open and short circuit detection
  • RTD current sources 1mA nominal>
  • 3 Wire Mode Not Supported
  • Each RTD uses one Analog Input channel
  • Analogue Outputs – 2 off


  • Each channel is an individually isolated current controlled 0 to 21mA output that can be used to sink or source power
  • Resolution: 14 bits
  • Accuracy: ± 0.1% at 23°C
  • Temperature Coefficient: 10ppm / °C
  • Minimum Load Loop resistance: Safe down to zero Ohms from +32V external supply
  • Maximum Load Loop resistance: 1000 Ohms when powered from +24V external
  • Maximum External Supply: 32 Volts
  • Output Form: Isolated active current controller
  • Number of field connections: 2 terminals per channel
  • Update time: 500mSec to within 1%
  • ???

    Type of Input Differential voltage inputs
    Input Range 0 to +5.15V or 0 to 21.5mA

    +5°C to +45°C

    ± 0.020% of reading from 1.0 to 5.15V and
    ± 0.025% of reading from 4.0 to 21.5mA

    -25°C to +55°C

    ± 0.025% of reading from 1.0 to 5.15V and
    ± 0.030% of reading from 4.0 to 21.5mA

    -40°C to +85°C

    ± 0.050% of reading from 1.0 to 5.15V and
    ± 0.065% of reading from 4.0 to 21.5mA